AC Won't Cool Past 76 Degrees in Seabrook
Seabrook · June 2026 · Brandon & Christian · From our service records

What the customer reported
A Seabrook homeowner reported that their air conditioner was not cooling past 76.
What we found and did
Brandon and Christian found a crack in the suction line outside and the unit grossly undercharged. They recovered the remaining refrigerant, repaired the leak on the suction line, and replaced the filter drier. The team then nitrogen pressure tested the system to 340 psi and performed a triple evacuation to reach an ultimate vacuum of 315 microns.
Result
The system was recharged with 6 lbs of R-410A to reach proper levels.