Thermostat Went Black and AC Quit in Houston 77550

Houston · November 2026 · Adrian · From our service records

Thermostat Went Black and AC Quit in Houston 77550

What the customer reported

The customer reported that the thermostat was black and the AC was not working.

What we found and did

Adrian found that the fan motor was out and the contactor was stuck on. He believed the contactor got stuck and over heated the fan motor and tripped the breaker. Adrian replaced the fan motor, fan blade, and contactor.

Smoke Smell After a Power Outage in Houston

Houston · September 2026 · Brandon, Gabriel & Christian · From our service records

Smoke Smell After a Power Outage in Houston

What the customer reported

After a power outage, the system came back on and the occupants said they smelled smoke, so the fire department shut off the system at this commercial property in the 77550 area.

What we found and did

Brandon, Gabriel, and Christian found that the blower motor drive and blower motor fuses had been bypassed and the motor was wired to constant power, which caused the motor to over amp and catch on fire; they also found a bad condenser fan relay. The team replaced the blower motor and belt (leaving a spare belt inside the unit), replaced the 10 amp fuses and rewired them back into the circuit, and added a 3 pole contactor in place of the failed VFD drive. They also replaced the outdoor fan contactor and rewired the thermostat to have a common wire and no batteries.

Result

The crew verified operation of both refrigeration circuits, the condenser fan motors, the blower motor with proper belt tension, and high and low stage, recording a 24° temp drop across the unit in high stage.

What Caused Air Balancing Problems in a Houston Business?

Houston · August 2026 · Brandon & Christian · From our service records

What Caused Air Balancing Problems in a Houston Business?

What the customer reported

A commercial customer in the 77550 area of Houston reported having air balancing problems.

What we found and did

Brandon and Christian found a shredded blower belt, a bad condenser fan motor, and a thermostat that was improperly programmed and not wired for 2 stage functionality, meaning the unit had never operated at full capacity. They also found the thermostat in suite 170 turned up, which kept the unit serving the shared space from removing humidity. They replaced and properly tensioned the blower belt (leaving a spare inside the blower compartment), replaced the condenser fan motor, and rewired the thermostat at both the thermostat and the unit so the 2nd stage could run, then reprogrammed, tested, and labeled the thermostat. They also lowered the suite 170 set point from 75 to 72 for more run time to pull humidity, blew out all unit drains, and unblocked one roof drain.

Result

After testing, operation was restored and the unit's 2nd stage ran for the first time, letting it operate at full capacity.

Show 1 more job

Water Leaking Through the Ceiling of a Houston Business

Houston · June 2026 · Adrian · From our service records

Water Leaking Through the Ceiling of a Houston Business

What the customer reported

A commercial customer in the 77550 area of Houston reported water leaking into the building.

What we found and did

Adrian found several pans in the ceiling space that had water in them, and determined the problem was coming from leaks in the roof rather than the HVAC system. The visit was a commercial diagnostic service to trace the source of the water.

Need commercial HVAC in Houston? Call us or book a time.

5.0 stars from 129 Google reviews

Explore more

Related services and areas

More ways we can help in Houston.

FAQ

Commercial HVAC in Houston: questions answered

Answered by our licensed technicians serving Houston.

How long does a commercial HVAC installation take?

Depending on system complexity and building size, most commercial installations take 1-4 weeks. We create detailed project timelines and coordinate around your business operations to minimize disruption.

Do you handle permits and inspections for commercial projects?

Yes, we handle the permitting process, including mechanical permits and coordination with the local building department in the city where your property sits.

What brands do you install for commercial systems?

We install and service major brands, including Carrier, Trane, and Lennox commercial equipment, and we select equipment based on your specific requirements, budget, and coastal durability needs.

Can you upgrade our commercial HVAC without shutting down the building?

In most cases, yes. We design phased installation plans that maintain partial climate control throughout the project, keeping your business operational during the transition.

Schedule Your $125 Diagnostic

Step 1 of 2

What do you need?

Tap the closest match.

When works best? (optional)

Licensed & Insured

Fully licensed and insured for your protection

24/7 Emergency

Available when you need us most

11+ Years

Over a decade of trusted service

ScheduleCall now